Three-Position Disconnector - Siemens 8DJH Installation And Operating Instructions Manual

Medium-voltage switchgear
Table of Contents

Advertisement

Description
Motor operating
mechanism
Releases
Shunt release (-Y1, -Y3)
28/121
Rated currents of the motor protection equipment (protection equipment with tripping
characteristic type C):
Rated supply voltage [V]
24 DC
48 DC
60 DC
DC/AC 110 (50/60 Hz)
DC 120/125
220 DC
AC 230 (50/60 Hz)
The control voltage (including releases) is protected with 8 A.
Releases trip the switch-fuse combination. The electrical opening command is transmitted to
the OPEN latch via a magnet armature by unlatching an energy store. Depending on the
operating mechanism used, up to 2 releases can be used.
Shunt releases (optional) are used to trip or electrically open the switch-fuse combination. The
opening command is executed by application of an auxiliary voltage (AC or DC, depending on
the design option). After opening the switch-fuse combination, the release is de-energized
internally.
Power consumption of the operating coils
Operating coil
Shunt release (-Y1, -Y3)
8.3

Three-position disconnector

Switching capacity and classification for disconnector and make-proof earthing switch
according to IEC/EN 62271-102 / VDE 0671-102:
Disconnector
Rated voltage U
r
Rated normal current I
r
Number of mechanical operating cycles / Classification
Make-proof earthing switch
Rated voltage U
r
Rated short-circuit making current I
Number of short-circuit making operations / Classification
1
Design option
Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • 500-8067.9
Recommended rated current for the
protection equipment [A]
4
2
1.6
1.0
1.0
1.0
0.5
Power consumption [W/VA]
Switch-fuse combination
≤ 370
kV
A
n
kV
50 Hz
up to kA
ma
60 Hz
up to kA
n
7.2
12
15
17.5
250, 630
1000 / M0
7.2
12
15
17.5
63
65
5 / E2
24
24
1
50/52.5
1
52/55