Switchgear Maintenance; End Of Life - Siemens 8DJH Installation And Operating Instructions Manual

Medium-voltage switchgear
Table of Contents

Advertisement

Maintenance
Checking the dew point
Checking the gas quality
Test operation
Replacement of
components
SF
gas
6
Recycling
500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05
9

Switchgear maintenance

8DJH switchgear is maintenance-free under normal ambient conditions according to
IEC 62271-1. Inspection or testing of the secondary equipment such as the capacitive voltage
detecting system is done within the scope of locally applicable laws and regulations.
The dew point needs no checking throughout the entire service life.
The gas quality needs no checking throughout the entire service life.
A function test of the switching devices is required only at the time of commissioning,
modification or retrofit at the panel.
Due to the fact that all parts of this switchgear have been optimized to last the normal service
life, it is not possible to recommend particular spare parts.
Information required for spare part orders of single components and devices:
• Type and serial number of the switchgear (see rating plates)
• Description or identification of the device or part on the basis of a sketch, a photo or a circuit
diagram
10

End of life

NOTE
The equipment contains the fluorinated greenhouse gas SF
with a global warming potential (GWP) of 22 800
released into the atmosphere.
➭ For use and handling of SF
4: Use and handling of sulphur hexafluoride (SF6) has to be observed.
1)
Source: "Regulation (EU) No 517/2014 of the European Parliament and of the Council of 16th April 2014 on
fluorinated greenhouse gases and repealing Regulation (EC) No 842/2006"
Before recycling the materials, evacuate the SF
use. For further information, please contact the Siemens Service Hotline.
The switchgear is an environmentally compatible product.
The components of the switchgear can be recycled in an environmentally compatible way by
dismantling into sorted scrap and residual mixed scrap.
After evacuating the SF
gas, the switchgear mainly consists of the following materials:
6
• Steel (enclosure and operating mechanisms)
• Stainless steel (vessel)
• Copper (busbars)
• Silver (contacts)
• Cast-resin based on epoxy resin (bushings and post insulators)
• Plastic materials (switching devices and fuse tripping)
• Silicone rubber
The switchgear can be recycled in ecological manner in compliance with existing legislation.
Auxiliary devices such as short-circuit indicators have to be recycled as electronic scrap.
Any existing batteries have to be recycled professionally.
As delivered by Siemens, the switchgear does not contain hazardous materials as per the
Hazardous Material Regulations applicable in the Federal Republic of Germany. For operation
in other countries, the locally applicable laws and regulations must be observed.
For further information, please contact the Siemens Service Hotline.
1)
. SF
has to be reclaimed and must not be
6
, IEC 62271-4: High-voltage switchgear and controlgear - Part
6
gas professionally and prepare it for further
6
Description
registered by the Kyoto Protocol
6
45/121