Siemens 8DJH Installation And Operating Instructions Manual page 30

Medium-voltage switchgear
Table of Contents

Advertisement

Description
Closing time
Opening time
Arcing time
Break time
Close-open contact time
Motor operating
mechanism
Closing solenoid (-Y9)
30/121
Designation
Component (item designation)
OPEN
1st shunt release
Additional
release
1
For operation of the switchgear beyond the range defined by IEC 60721-3-3 Class 3K4,
a minimum command duration of 100 ms is recommended.
The interval of time between the initiation (command) of the closing operation and the
instant when the contacts touch in all poles.
The interval of time between the initiation (command) of the opening operation and the
instant when the contacts separate in all poles.
The interval of time from the first initiation of an arc and the instant of final arc extinction in
all poles.
The interval of time between the initiation (command) of the opening operation and the
instant of final arc extinction in the last-pole-to-clear (=opening time and arcing time).
The interval of time - in a make-break operating cycle - between the instant when the contacts
touch in the first pole in the closing process, and the instant when the contacts separate in all
poles in the subsequent opening process.
Power consumption of circuit-breaker motor operating mechanism
Circuit-breaker
Max. power consumption
DC
Type 2
approx. 80 W
Rated current for the motor protection equipment
Rated supply voltage
[V]
DC 24
DC 48
DC 60
DC/AC 110 (50/60 Hz)
DC 220 / AC 230 (50/60 Hz)
1 M.c.b. with C-characteristic
The supply voltage may deviate from the rated supply voltage specified in the table by
max. -15% to +10%.
Breaking capacity of auxiliary switch 3SV92
Breaking capacity
Operating voltage [V] Normal current [A]
AC 40 Hz to 60 Hz
up to 230
DC
24
48
60
110
220
The closing solenoid closes the circuit-breaker electrically. The closing command is executed
by application of an auxiliary voltage (AC or DC, depending on the design option). After
closing, the closing solenoid is de-energized internally.
Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • 500-8067.9
2nd shunt release
C.t.-operated release
Undervoltage release
Low-energy release
AC
approx. 80 VA
1
Recommended rated current for the protection equipment
[A]
Circuit-breaker type 2
8
6
4
2
1.6
10
Resistive load
10
10
9
5
2.5
Unit
Time
Type 2
(-Y1)
ms
< 40
(-Y3)
ms
< 40
(-Y6)
ms
< 20
(-Y7)
ms
< 20
(-Y6)
ms
< 20
Inductive load
10
9
7
4
2