Phase Sequence; Insulating Gas; Dielectric Strength And Site Altitude - Siemens 8DJH Installation And Operating Instructions Manual

Medium-voltage switchgear
Table of Contents

Advertisement

Gas leakage rate
Dielectric strength
Site altitude
500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05
8.8

Phase sequence

Phase sequence for all panel types 8DJH:
Fig. 19:
View from the front
8.9

Insulating gas

The sealed pressure system of the switchgear contains the insulating gas SF
greenhouse gas, GWP 22,800).
Example for a typical amount of SF
The respective amount of SF
The gas leakage rate is < 0.1% per year (referred to the absolute gas pressure).
8.10

Dielectric strength and site altitude

• The dielectric strength is verified by testing the switchgear with rated values of short-
duration power-frequency withstand voltage and lightning impulse withstand voltage
according to IEC 62271-1/VDE 0671-1.
• The rated values are referred to sea level and to normal atmospheric conditions (101.3 hPa,
3
20 °C, 11g/m
humidity according to VDE 0111 and IEC 60071).
• The dielectric strength decreases with increasing altitude. For site altitudes above 1000 m
(above sea level) the standards do not provide any guidelines for the insulation rating, but
leave this to the scope of special agreements.
All parts housed inside the switchgear vessel which are subjected to high voltage are SF
insulated against the earthed enclosure.
The gas insulation in the switchgear vessel at a relative gas pressure of 50 kPa (= 500 hPa)
permits switchgear installation at an altitude of up to 2000 m above sea level without the
dielectric strength being adversely affected. This also applies to the cable connection when
using screened cable plugs. Site altitudes above 2000 m are possible on request.
For site altitudes of more than 1000 m (above sea level), the decrease (reduction) of the
dielectric strength must be considered for panels with HV HRC fuses. For these site altitudes, a
higher insulation level must be selected, which results from the multiplication of the rated
insulation level for 0 to 1000 m with the altitude correction factor K
Fig. 20:
View from the left
gas: Panel block 8DJH RRT with 2.2 kg SF
6
gas included is indicated on the rating plate of the switchgear.
6
Description
(fluorinated
6
(CO
e = 50t).
6
2
-
6
.
a
35/121