500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05
➭ Fasten the surge arrester plate with 2 hexagon head bolts M8x16 ① and plain washers ② to
the upper cross member.
Fig. 39:
Fastening the surge arrester plate
➭ Earth the cable shields with cable lugs and earthing bolts M10 at the upper cross member.
Fig. 40:
Earthing the cable shields
➭ Observe the minimum distances according to the manufacturer's instructions while
connecting non-screened cable plugs or surge arresters.
The use of RICS5xxx cable plugs with RDA in panels with a width of 310 mm is allowed
under normal ambient conditions despite the reduced distance (according to IEC 62271-1).
✔ The installation of the Raychem RICS5xxx cable plug with RDA is completed.
Installation
①
Cable shield, phase L1
②
Cable shield, phase L2
③
Cable shield, phase L3
④
Upper cross member