AS-i Speed Monitor
Configuration
5.
A 4-digit number can be entered. The factory default setting is password 0000.
The password must be set to a different value in order to run the device.
6.
In the next menu item the addresses of the safety-limited speed (SLS) are
assigned
First the previously set values are shown. These can be overwritten.
If the same address is entered for multiple channels, the results of these channels
are overlaid. Only if all frequencies for these channels are within the range of the
safety-limited speed is an SaW code sequence sent. This also makes it possible
for example to combine Channel 1 and 2 into a single address.
Channels for which 0 is entered as an address are deactivated.
7.
In the next menu item the addresses of the safety stop are assigned.
First the previously set values are shown. These can be overwritten.
If the same address is entered for multiple channels, the results of these channels
are overlaid. Only if all frequencies for these channels are within the range of the
safety-limited speed is an SaW code sequence sent. This also makes it possible
for example to combine Channel 1 and 2 into a single address.
Channels for which 0 is entered as an address are deactivated.
8.
After clicking on OK the following menu appears
Here the taught frequencies + 10% tolerance are shown.
9.
The displayed values can be overwritten. To deactivate a channel, set the
frequency to 0 or set no AS-i address.
10.
After clicking on OK the data are shown again.
11.
After clicking on OK the following menu appears
SPEED MONITOR
PASSWORD
xxxx
OK
ESC
ADDRESSES SLS
CH1 23
CH2 24
OK
ESC
ADDRESSES STOP
CH1 23
CH2 24
OK
ESC
FREQUENCY
CH1 23433
CH2 24355
OK
ESC
ADDR FREQUENCY
CH1-12-23433
CH2-13-24355
OK
ESC