3.2.3
SCN command
Parameter
Signal pattern
*******1
Ready1
****1***
End1
*1******
End2
*****1**
Wait1
***1****
Wait2
***1*1**
Wait*
******1*
Pump1 ?
**1*****
Pump2 ?
**1***1*
Pump* ?
3.2.4
CTL-Befehl
Parameter
Signal pattern
00000000000000
INIT
***0000*000**0
INIT 732/819
***000*******1
PROG R/S 1
******0*100***
PROG R/S 2
***001*******0
PUMP R/S 1
***010*******0
FILL A 1
***100*******0
INJECT A 1
***001*******1
FILL B/STEP 1
***110*******0
INJECT B 1
***011*******0
ZERO 1
************1*
PUMP 833 ein
************0*
PUMP 833 aus
***********1**
STEP MSM 833
*************1
Metrohm 838 Advanced Sample Processor, Appendix
In order to simplify the use of Remote commands, particularly when
several devices are linked together with Metrohm cables, predefined bi-
nary patterns are available as command parameters for the commands
CTL and SCN for standard conditions. These are:
Function
waits for "ready" condition of 732/1
waits for the EOD impulse from 732/1
waits for the EOD impulse from 732/2
waits for active Remote line 2 set by 732/1 or 797
waits for active Remote line 4 set by 732/2
waits for active Remote line 2 and 4 set by 732/1 and 732/2
waits for active IC pump 709/1
waits for active IC pump 709/2
waits for active IC pumps 709/1 and 709/2 laufen
Function
initializes the Remote interface
initializes the Remote lines of 732 or 819
starts/stops the time program of 819/1
starts/Stopps the time program of 819/2
starts/stops IC pump 818/1
switches valve A of 820/1 to "Fill"
switches valve A of 820/1 to "Inject"
switches valve B of 820/1 to "Fill"
switches valve B of 820/1 to "Inject"
activates autozero of 819/1
starts the pump of a 833
Stopps the pump of a 833
advances a step of the suppressor module 833
starts or advancesdevice 1 (e. g. 797 VA Com-
putrace)
3.2 The Remote interface
Signal
static
static
pulse (200 ms)
pulse (200 ms)
pulse (200 ms)
pulse (200 ms)
pulse (200 ms)
pulse (200 ms)
pulse (200 ms)
pulse (200 ms)
static
static
pulse (200 ms)
static