Omron NX Series User Manual page 179

Artificial intelligence machine automation controller
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

WebAPI Connection Function
Event name
WebAPI Connection Service Setting Error
Meaning
There is an error in the WebAPI connection service setting.
Source
PLC Function Module
Error attrib-
Level
utes
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
Setting error
Power was interrupted while the
setting was being downloaded.
Power was interrupted during the
Clear All Memory operation.
Power was interrupted during the
restore operation.
Non-volatile memory failed.
Attached in-
Attached information 1: Error details
formation
01 hex: Non-volatile memory access error
02 hex: WebAPI connection service setting is not correct
03 hex: Certificate management setting is not correct
04 hex: File upload setting is not correct
Attached Information 2: Only when attached information 1 is 3 or 4
Connection ID (01 hex-) (It corresponds to the combo box for selecting a destination in the WebAPI
Settings Tab Page on the AI Operator.)
Precautions/
None
Remarks
NX/NY-series Artificial Intelligence Machine Automation Controller User's Manual (W594)
Source details WebAPI
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Identify the error from the attach-
ed information, correct the set-
ting, and then download the set-
ting again.
Perform the Clear All Memory
operation or download the set-
tings.
Replace the AI Controller.
8 Troubleshooting
Event code
35F40000 hex
Detection tim-
ing
Automatic re-
Log category
covery
Not affected.
Name
---
Prevention
None
Do not interrupt the power supply
during download of the settings,
Clear All Memory, or restore op-
erations.
None
At power ON,
Controller re-
set, or when
downloading
settings
System
8
8-43

Advertisement

Table of Contents

Troubleshooting

loading