Omron NX Series User Manual page 171

Artificial intelligence machine automation controller
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

Event name
Feature Extraction Service TimeSeries Write Error
Meaning
Writing from the feature extraction service to TimeSeries failed.
Source
PLC Function Module
Error attrib-
Level
utes
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
The TSDB service was stopped.
The TSDB service was shut-
down.
There is insufficient free space in
the internal buffer of the TSDB
service.
The SD Memory Card was re-
moved. (for NX-series AI Control-
lers)
The expanded storage was re-
moved. (for NY-series AI Control-
lers)
Attached in-
None
formation
Precautions/
None
Remarks
NX/NY-series Artificial Intelligence Machine Automation Controller User's Manual (W594)
Source details FE/MLE
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Start the TSDB service.
Cycle the power supply to the AI
Controller and start the TSDB
service.
Increase the set value for the
task period of the primary peri-
odic task.
Decrease the number of
equipment events.
Insert an SD Memory Card.
Turn off the power supply to the
NY-series AI Controller and
mount the expanded storage,
and then turn on the power sup-
ply.
8 Troubleshooting
Event code
44710000 hex
Detection tim-
ing
Log category
Not affected.
Name
---
Prevention
---
Periodically
System
8
8-35

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents