Event name
Timeout Occurred
Meaning
A timeout occurred while records are added to TimeSeries or data exports to a CSV file.
Source
PLC Function Module
Error attrib-
Level
utes
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
The file access delayed due to
insufficient memory space or
memory error (access prohibited,
hardware failure, or locked).
Attached in-
Attached information 1: TimeSeries Name (beginning 15 characters)
formation
Attached Information 2: Cause of the error
0: Record addition timeout
1: Record writing or reading timeout during export
2: File open timeout during export
3: File close timeout during export
Precautions/
None
Remarks
NX/NY-series Artificial Intelligence Machine Automation Controller User's Manual (W594)
Source details TSDB
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Check the storage of the TimeS-
eries or the status, volume, and
write allowance setting of the
storage to which the CSV file is
exported.
8 Troubleshooting
Event code
65400000 hex
Detection tim-
ing
Access to the
Log category
database again
or execute to
access to the
Export file
Not affected.
Name
---
Prevention
Check the storage of the TimeS-
eries or the status, volume, and
write allowance setting of the
storage to which the CSV file is
exported, and then execute the
command.
During the ac-
cess to the da-
tabase or the
processing to
access to the
Export file
System
8