Omron NX Series User Manual page 170

Artificial intelligence machine automation controller
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

8 Troubleshooting
Attached in-
Attached information 1: Classification for identifying the cause of the error
formation
01 hex: Setting error
02 hex: Variable setting error
03 hex: Non-volatile memory access error
Attached information 2: Classification for identifying the cause of the error
When the value of attached information 1 is 1
01 hex: Setting error
When the value of attached information 1 is 2
01 hex: A variable that is not existed was specified
02 hex: A data type that is not permitted was specified
03 hex: A variable with the Constant attribute was specified for the output frame variable of the fea-
ture extraction.
Attached information 3: Classification for identifying the cause of the error. Only when the value of at-
tached information 1 is 1 or 2
65535: A setting error of the Feature Extraction Function shared by equipment events
0 to 127: Equipment event number where an error was detected first
(ID corresponding to the equipment event name in equipment event or data set registration on the AI
Operator)
Attached information 4: Number of equipment events that have a setting error
When the value of attached information 3 is 65535
0: Equipment event setting error
1: Setting error in linking with the Time Series Database
When the value of attached information 3 is from 0 to 127
1 to 128: Number of equipment events that have a setting error
Precautions/
None
Remarks
Event name
PLC System Processing Error
Meaning
An error was detected in the PLC Function Module.
Source
PLC Function Module
Error attrib-
Level
utes
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
An error occurred in the software
or hardware.
Attached in-
None
formation
Precautions/
None
Remarks
8-34
Source details FE/MLE
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Contact your OMRON represen-
tative.
NX/NY-series Artificial Intelligence Machine Automation Controller User's Manual (W594)
Event code
446F0000 hex
Detection tim-
ing
Cycle the pow-
Log category
er supply.