IMD 100 Integration manual 4189360015 Rev. G
The mains wires are connected as follows:
Terminal no.
Terminal text
PE,
X1, Mains, 5
L1
X1, Mains, 6
L2
X1, Mains, 7
L3
The IMD is not sensitive to the order of the phases.
See IMD 100 Installation instructions for instructions about how to use the connectors.

5.2.3 Safe energy connection requirements

Safe energy source can be either batteries or ultra-caps. See IMD 100 Datasheet for Safe energy
specifications.
Requirements for external components connected to the SE input:
www.deif.com/wind-power
IMD 122 C
IMD 135 C
Description
Protective earth from mains supply. The minimum size of
the protective earth conductor must comply with local
safety regulations for high protective earthing conductor
current.
L1 Mains power input
L2 Mains power input
L3 Mains power input
Electrical HW connections and requirements
IMD 122 B and early
production of IMD 122 C
Page 34 of 243