Mains Supply Connections Requirements - Deif IMD 100 Series Integration Manual

Integrated motor drive
Table of Contents

Advertisement

IMD 100 Integration manual 4189360015 Rev. G
Terminal no.
Terminal text
PE,
X1, Motor, 10
W
X1, Motor 11
V
X1, Motor, 12
U
See IMD 100 Installation instructions for instructions about preparing the motor cable for connections,
and how to use the connectors.

5.2.2 Mains supply connections requirements

The mains connection is used to connect the IMD to the grid. The connection must have protective
earthing. The IMD supports all earthing system types defined in BS 7671 (TN-S, TN-C-S, TT, TN-C,
and IT).
Attention
The IMD must not be operated without connection to protective earthing. The mains supply
must never exceed the range specified in the Data sheet. Risk of destruction of the IMD.
See IMD 100 Datasheet for mains input specifications.
Requirements for external components connected to the Mains input:
EMC filters
Main circuit
breaker
Fuses
* In environment with very high electromagnetic interference or total harmonic disturbance it might be
necessary to use an external EMC filter and/or line choke.
See
Table 2
on page
The protective earth wire is connected to X1, PE terminal.
IMD 122 C and IMD 135 C: Phoenix AKG 16 GN flat blade screws terminal.
IMD 122 B and early production of IMD 122 C: M5 threaded rod with nuts and washers. Suitable cable
lugs for the used wires (not delivered) are needed for the connection.
www.deif.com/wind-power
Not needed *. Built-in EMC filter and input DC-link filter capacitors eliminates the
need for external filters. Leakage current is less than 60mA.
Optional.
Mandatory. Use maximum 32 A fuse type F, FF, or semiconductor automatic
type D.
26
(PLH 16) for suitable wire cross section.
Electrical HW connections and requirements
Description
Protective earth for motor output. The minimum size of
the protective earth conductor must comply with local
safety regulations for high protective earthing conductor
current.
W motor output
V motor output
U motor output
Page 33 of 243

Advertisement

Table of Contents
loading

This manual is also suitable for:

Imd 122 bImd 122 cImd 135 cImd 122 a

Table of Contents