IMD 100 Integration manual 4189360015 Rev. G
10. Click on Device → Flash... to open the upgrade dialogue:
11. Ensure that all three checkboxes are ticked and click Start.
12. When the programming cycle is completed, set the IMD back to normal operation mode:
a. Turn the 24 V DC (or the 400 V AC if the DC power supply is built-in) off.
b. Set the CAN ID switch back to its original position.
c. Turn the 24 V DC (or the 400 V AC if the DC power supply is built-in) on. Note that the first
startup after firmware upgrade might take longer (up to approximately 10 s).
13. The IMD is now updated.
Info
On rare occasions, The SDFlash program will show a "Connection error" after step
page
154
1. Close the SDflash program
2. Turn off the IMD
3. Start the SDflash
4. Turn on the IMD
5. Repeat com configuration, and the actions described in steps
page

9.16.2 Updating firmware with CANopen files through USB "service" connector method

Updating firmware with CANopen files, requires that a bootloader is installed as well. Once the
bootloader is installed (see section
section
9.16.2.3
on page
9.16.2.1
Prerequisites
A computer with Spectrum Digital SDFlash program installed (including V3.3 SDFlash serial patch
for flash programming, September 5, 2008), (http://emulators.spectrumdigital.com/utilities/sdflash/)
Typically, the necessary USB driver will be found automatically if the computer is on-line.
Otherwise, go to Silicon Labs home page and download the latest driver for CP210x USB to UART
Bridge (http://www.silabs.com/products/mcu/Pages/USBtoUARTBridgeVCPDrivers.aspx).
Info
The links above were valid at the time when this manual was written. If the link does
not work anymore, search for "V3.3 SDFlash serial patch" or "CP210x USB to
UART Bridge driver".
www.deif.com/wind-power
is executed. In such a case, it is necessary to restart the whole process:
154
.
9.16.2.2
on page
160
or section
9.16.3
155
), it is enough to install only the FW file (see
on page
164
depending on the method).
Operational procedures
11
on
4
on page
151
to
13
on