Specifications (Cooling and Air-Conditioning Requirements) (Continued)
TABLE 2-4
Name
Power Cabinet (SPARC
Enterprise M8000 server)
Power Cabinet (for SPARC
Enterprise M9000 server base
cabinet)
Power Cabinet (for SPARC
Enterprise M9000 server base
cabinet + expansion cabinet)
* Heat dissipation varies by power consumption. Determine the power consumption based on the actual system configuration and then
confirm the right value.
† The heat dissipation, exhaust airflow and acoustic noise value of the Power Cabinet is included in the value for the SPARC Enterprise
M8000 server or SPARC Enterprise M9000 server.
‡
At an installation altitude ranging from 0 to less than 400 m (1312 feet) above sea level, you can select overfloor cooling as the cooling
method of the server.
Electrical Specifications
Section 3.3 of the Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide will
be updated with the following tables.
Specifications
TABLE 2-5
NAME
SPARC Enterprise M8000 server
SPARC Enterprise M9000 server (base cabinet)
SPARC Enterprise M9000 server
(base cabinet + expansion cabinet)
* The values for maximum power consumption and apparent power vary by the type of CPU mounted. To plan the installation of a serv-
er equipped with different types of CPU, use the CPU of larger power consumption as a basis. For the types of CPU, see Section 3.3.6,
"CPU Types and Server Maximum Power Consumption"of the Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide.
32
Sun SPARC Enterprise M8000/M9000 Servers Product Notes for XCP 1091 • May 2010
Heat
Exhaust
dissipation
airflow
[kJ/h]
[cmh(m3/h)]
†
†
-
-
†
†
-
-
†
†
-
-
*
(Single-Phase Power Requirements)
Power consumption [kW]
3.88-10.49
6.20-19.87
11.92-39.72
Cooling method
Overfloor/underfloor
Overfloor/underfloor
‡
Underfloor
Apparent power [kVA]
4.11-11.12
6.58-21.07
12.64-42.13
Noise
Air-conditioning
level
type
[dBA]
†
Forced air
-
cooling
†
Forced air
-
cooling
†
Forced air
-
cooling