Ambient Environmental Requirements

The table found in Section 2.2.1 of the Sun SPARC Enterprise M8000/M9000 Servers
Overview Guide will be updated with the information in
Ambient Environmental Requirements
TABLE 2-2
Operating Range
Ambient
5˚C to 32˚C
temperature
(41˚F to 89.6˚F)
Relative
20% RH to 80% RH
*
humidity
Altitude
3,000 m (10,000 ft)
restriction
Temperature
5˚C to 32˚C (41˚F to 89.6˚F) at an
installation altitude ranging from 0 to less
conditions
than 1500 m (4921 feet) above sea level
5˚C to 30˚C (41˚F to 86˚F) at an
installation altitude ranging from 1500 m
(4921 feet) to less than 2000 m (6562 feet)
above sea level
5˚C to 28˚C (41˚F to 82.4˚F) at an
installation altitude ranging from 2000 m
(6562 feet) to less than 2500 m (8202 feet)
above sea level
5˚C to 26˚C (41˚F to 78.8˚F) at an
installation altitude ranging from 2500 m
(8202 feet) to 3000 m (9843 feet) above sea
level
* There is no condensation regardless of the temperature and humidity.
† All altitudes are above sea level.
TABLE 2-2
Non-Operating Range
Unpacked:
0˚C to 50˚C (32˚F to 122˚F)
Packed:
-20˚C to 60˚C (-4˚F to 140˚F)
to 93% RH
12,000 m (40, 000 ft)
Chapter 2
Information About Hardware
, below.
Optimum
21˚C to 23˚C
(70˚F to 74˚F)
45% RH to 50% RH
21