Installation Requirements
Control Wiring
8.
Wire control to the control board.
Note: Drive default is programmed for
external interlock.
Mandatory Ground Wiring
Be sure to pull a dedicated low impendance
ground wiring from customer power to drive
and ground wire from drive to motor.
Utility
Drive
Motor Ground
I/O Connection
Run 110 Vac and 24 Vdc control wiring
in separate conduit
Communication wire to be shielded
Terminal Block Layout
21
22
23
24
25
26
RO1
RO1
RO1
RO2
RO2
RO2
NC
COM
NO
NC
COM
NO
12
13
14
15
16
17
18
24 Vdc
GND
DI4
DI5
DI6
COM
AO1+
out
DI1 6
1
2
3
4
5
6
7
+10
AI1+
AI1
AI2+
AI2
24 Vdc
GND
Vdc
out
Factory Jumper
External Interlock
28
H-Max Series Adjustable Frequency Drive MN04008005E—September 2011
Optional
Circuit
Breaker
Factory
Jumper
(Inside Motor
Conduit Box)
Analog
32
33
RO3
RO3
COM
NO
19
30
A
B
AO1
24 Vdc
RS 485
RS 485
in
Data
Data+
8
9
10
11
DI1
DI2
DI3
COM
DI1 6
BACnet/IP Ethernet ndustrial Protocol
RJ-45
Modbus/TCP Transmission Control Protocol (Ethernet Based)
5% DC L nk
L1
Three-Phase Input
Reactor
Input
L2
(Single-Phase not available)
L3
Slot A
Terminal
Factory Default Signal
1
+10V
Reference Output
Resistor
Analog Input Voltage (Range 0–10 Vdc)
AI–1+
2
(can be programmed to current 4–20 mA)
3
V
Analog Output Common (Ground)
in
Analog Input Current (Range 4–20 mA)
4
AI–2+
(can be programmed to voltage 0–10 Vdc)
PI Setpoint or Feedback
Analog Input Common
5
AI–2–
PI Setpoint or Feedback
6
24V
Control Voltage Output (0.1A max.)
out
GND
I/O Ground
7
8
DIN1
START/STOP (Contact closed = start)
9
DIN2
External Fault (Closed = fault)
Run Interlock Permissive IP Interlock
10
DIN3
(Closed = OK)
11
COM
DIN1–DIN6 Common
12
24V
Control Voltage Output (0.1A max.)
out
13
GND
I/O Ground
14
DIN4
Speed Select 0–100% (Preset speed)
DIN5
Fire Mode (Contact closed = fire mode)
15
16
DIN6
Force Bypass (Contact closed = bypass)
CMB
17
DIN1–DIN6 Common
18
AO–1+
Output Frequency (0–20 mA)
19
AO–1–
Analog Output Common (Ground)
30 24 Vdc
Auxiliary Input Voltage
in
DATA-
RS-485 DATA-
A
B
DATA+
RS-485 DATA+
Relay Board 1
21
Default Signal
22
RO1 Bypass Run
23
24
25
RO2 Drive Run
26
32
RO3 Fault
33
R+
No
Function
R-
U (T1)
Three-Phase
V (T2)
Output
W (T3)
ON
CURRENT
CURRENT
CURRENT
Programmable BACnet,
Modbus, FLN, N2
Slot B
24 Vdc/8A
250 Vac/8A
125 Vdc/0.4A
Motor
Test
OFF
RS485
VOLTAGE
AO1
VOLTAGE
AI2
VOLTAGE
AI1