H-Max Technical Data

Description
Attribute
Mains connection
Input voltage U
Input frequency
Connection to mains
Starting delay
Motor connection
Output voltage
Continuous output current
Output frequency
Frequency resolution
Control characteristics Switching frequency
Frequency reference
Analog input
Panel reference
Field weakening point
Acceleration
Deceleration
Ambient conditions
Ambient operating temperature
Storage temperature
Relative humidity
Air quality:
Altitude
Vibration:
-
-
Shock:
-
-
Enclosure class
in
-
Chemical vapors
-
Mechanical particles
EN61800-5-1
EN60668-2-6
EN61800-5-1
EN60068-2-27
H-Max Installation Manual Addendum
Specification
525-600V, -10 to 10%
50-60 Hz, -5 to 10%
Once per minute or less
6s (FS5 to FS6); 8s (FS7 to FS9)
0-Uin
I
: Ambient temperature maximum 40°C, up to 50°C with
L
derating, overload 1.1 x I
(1min./10 mins)
L
0-320 Hz
0.01 Hz
FS5-FS9: 1.5-6 kHz
Default: 2 kHz
For a product that is configured for a C4 installation on IT
network the maximum switching frequency is limited to
default 2kHz.
Automatic switching frequency derating in case of
overload.
Resolution 0.1% (10-bit), accuracy +1%
Resolution 0.01 Hz
8–320 Hz
0.1–3000 sec.
0.1–3000 sec.
I
: –10°C (no frost) to 40°C, up to 50°C with derating
L
–40° to 70°C
0–95% R
, non-condensing, non-corrosive
H
Tested according to IEC 60068-2-60 Test Ke: Flowing
mixed gas corrosion test, Method 1 (H
sulfide] and SO
[sulfur dioxide]
2
Designed according to:
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to 1000m
1% derating for each 100m above 1000m
Max. altitudes:
525–600V: 2000m (TN and IT systems, no corner
grounding)
Voltage for I/O signals:
Up to 2000m: Allowed up to 240V
2000–4500m: Allowed up to 120V
5–150 Hz
Displacement amplitude:
1 mm (peak) at 5–15.8 Hz (FS4–FS9)
Maximum acceleration amplitude:
1g at 15.8–150 Hz (FS4–FS9)
UPS drop test (for applicable UPS weights)
Storage and shipping: Maximum 15g, 11 ms (in package)
IP21/Type 1 standard in entire kW/hp range
IP54/Type 12 option
Note: Keypad required for IP54/Type12