Catalog Number Selection; H-Max Series Open Drives - Eaton H-Max Series Installation Manual

Adjustable frequency drive
Hide thumbs Also See for H-Max Series:
Table of Contents

Advertisement

H-Max Series Overview

Catalog Number Selection

H-Max Series Open Drives

HMX 3 4 A G 3D4 2 1 - N
Product
HMX = HVAC drive
Phase
3 = Three-phase
Voltage
Software Series
2 = 200–240V
A–Z
4 = 380–480V
Keypad
G = Graphical panel
Notes
All boards are varnished (conformed coated). Corrosion resistant.
Battery included in all drives for real-time clock. Three year lifetime.
Keypad kit includes HOA bypass.
Keypad kit includes HOA, back reset for Europe application.
EMI/RFI filters included.
DC link choke included.
16
H-Max Series Adjustable Frequency Drive MN04008005E—September 2011
N = No brake chopper
1 = Open NEMA Type 1 IP21
2 = Open NEMA Type 12 IP54
Input Options Frame
and Voltage Specific
2 = EMC C2
Amperes
200–240 Volts
380–480 Volts
3D7 = 3.7A—0.75 hp, 0.55 kW
3D4 = 3.4A—1.5 hp, 1.1 kW
4D8 = 4.8A—1 hp, 0.75 kW
4D8 = 4.8—2 hp, 1.5 kW
6D6 = 6.6A—1.5 hp, 1.1 kW
5D6 = 5.6A—3 hp, 2.2 kW
8D0 = 8A—2 hp, 1.5 kW
8D0 = 8A—4 hp, 3 kW
011 = 11A—3 hp, 2.2 kW
9D6 = 9.6A—5 hp, 4 kW
012 = 12A—4 hp, 3 kW
012 = 12A—7.5 hp, 5.5 kW
018 = 18A—5 hp, 4 kW
016 = 16A—10 hp, 7.5 kW
024 = 24A—7.5 hp, 5.5 kW
023 = 23A—15 hp, 11 kW
031 = 31A—10 hp, 7.5 kW
031 = 31A—20 hp, 15 kW
048 = 48A—15 hp, 11 kW
038 = 38A—25 hp, 18.5 kW
062 = 62A—20 hp, 15 kW
046 = 46A—30 hp, 22 kW
075 = 75A—25 hp, 18.5 kW
061 = 61A—40 hp, 30 kW
088 = 88A—30 hp, 22 kW
072 = 72A—50 hp, 37 kW
105 = 105A—40 hp, 30 kW
087 = 87A—60 hp, 45 kW
140 = 140A—50 hp, 37 kW
105 = 105A—75 hp, 55 kW
170 = 170A—60 hp, 45 kW
140 = 140A—100 hp, 75 kW
205 = 205A—75 hp, 55 kW
170 = 170A—125 hp, 90 kW
261 = 261A—100 hp, 75 kW
205 = 205A—150 hp, 110 kW
310 = 310A—125 hp, 90 kW
261 = 261A—200 hp, 132 kW
310 = 310A—250 hp, 160 kW
Braking/Application
Standard Onboard Communications
(low overload)
BACnet MS/TP = Master slave/token protocol
(Universal BACnet) RS-485
Modbus RTU RS-485, ASCII or RTU, remote terminal
Enclosure
unit 32 nodes
N2 = Johnson Controls
Onboard Ethernet-Based Communications
BACnet/IP Ethernet industrial protocol
Modbus/TCP Transmission control protocol
(Ethernet-based)
RS-485 Communications
®
®
Metasys
N2 network
(port left side of keypad)