General; Catalog/Style Numbering - Eaton H-Max Series Manual

Drives intellipass/intellidisconnect frames 4-7
Hide thumbs Also See for H-Max Series:
Table of Contents

Advertisement

General

General
This document provides supplement information to the H-Max installation Manual MN04008005E specific to the H-Max
IntelliPass and IntelliDisconnect products. These products are offered with input/output voltages of 208, 230 & 480 VAC with
HP ranges from 1 to 75hp. Both UL Type 1,12 and Type 3R enclosures are available along with several factory wired power
and plug in options.
For drive setup and operation I.e. Application, Keypad use, Drive and motor parameters setup, see the quick start guide
MN04008005E included with the drive. The drive start up wizard can be used to complete the process. For more information
on speed control and other H-Max drive features see H-Max Application Manual MN04008006E. The Application Manual and
can be found at
http://www.eaton.com/Electrical/USA/ProductsandServices/Automation and Control/Adjustable Frequency Drives/H-Max/
index.htm

Catalog/Style Numbering

Eaton HMAX IntelliPass and IntelliDisconnect Catalog Number Matrix
Product:
HMX = HVAC Drive (VT)
Enclosure/Style:
3 = IntelliPass NEMA Type 1
4 = IntelliPass NEMA Type 12
5 = IntelliPass NEMA Type 3R
A = IntelliDisconnect NEMA Type 1
B = IntelliDisconnect NEMA Type 12
C = IntelliDisconnect NEMA Type 3R
NEC 208 Volts:
NEC 230 Volts:
4D6 = 4.6 Amp = 1.0 HP
4D2 = 4.2 Amp = 1.0 HP
7D5 = 7.5 Amp = 2 HP
6D8 = 6.8 Amp = 2 HP
011 = 11 Amp = 3 HP
9D6 = 9.6 Amp = 3 HP
017 = 17 Amp = 5 HP
016 = 16 Amp = 5 HP
025 = 24 Amp = 7.5 HP
022 = 22 Amp = 7.5 HP
031 = 31 Amp = 10 HP
028 = 28 Amp = 10 HP
047 = 47 Amp = 15 HP
042 = 42 Amp = 15 HP
060 = 60 Amp = 20 HP
054 = 54 Amp = 20 HP
075 = 75 Amp = 25 HP
068 = 68 Amp = 25 HP
088 = 88 Amp = 30 HP
080 = 80 Amp = 30 HP
104 = 104 Amp = 40 HP
Notes:
All Boards are Varnished
Battery Included in all drives for real time clock
EMC = EMC C2 Standard
Graphic keypad on all drives
Bypass & HOA Keypad
4
H-Max Series Drives IntelliPass®/IntelliDisconnect® IL04008003E April 2013 www.eaton.com
HMX 011
3
Voltage:
Braking:
1 = 208V
2 = 230V
N = No Brake Chopper
4 = 480V
(Low Overload)
5 = 575V
B = Internal Brake
Chopper Low
NEC 480 Volts:
2D1 = 2.1 Amp = 1 HP
3D4 = 3.4 Amp = 2 HP
5D6 = 5.6 Amp = 3 HP
7D6 = 7.6 Amp = 5 HP
011 = 11 Amp = 7.5 HP
014 = 14 Amp = 10 HP
021 = 21 Amp = 15 HP
027 = 27 Amp = 20HP
034 = 34 Amp = 25 HP
040 = 40 Amp = 30 HP
052 = 52 Amp = 40 HP
065 = 65 Amp = 50 HP
077 = 77 Amp = 60 HP
096 = 96 Amp = 75 HP
4
N
A
P3
Software Options:
A - Standard
Intellipass/Options:
00 =None
P3 = Drive Isolation Fuses
(for FS 4-7 not available with M1, P6 or PE options)
P6 = Drive Isolation Contactor includes drive test switch
(For FS 4-7 not available with M1, P3 or PE options)
L4 = Pilot Lights (not available with M1)
M1 = Manual Bypass - includes pilot lights and Isolation contactor (not
available with any other wired option)
IS = Isolation Switch not available with M1, P6 or PE options
SA = Space Heater w/Xformer (Type 3R only)
K9 = Aux Contacts
Intellidisconnect Options:
00 = None
P3 = Drive Isolation Fuses
PE = Drive Output contactor
L3 = HMAX Pilot Lights
SA = Space Heater w/Xformer (Type 3R only)
K9 = Aux Contacts
Extended I/O Options in Slot D & E:
B1 = 6 DI or DO, 1 ext +24V DC/EXT +24V DC Programmable
B2 = 1 RO (NC/NO), 1 RO (NO), 1 Thermistor
B4 = 1 AI (mA isolated), 2 AO (mA isolated)
B5 = Card-3 Relay Dry Contact
B9 = 1 RO (NO), 5 DI 42 – 240V AC Input
BF = Expander IO - 1*AO, 1*DO, 1*RO
I/O Options in Slot B
F2 = 2 relay and 1 Thermistor- not available with L3/L4 Pilot light
option replaces standard Relay1 pcb in Slot B and Fault Relay function
Optional Communications in Slot D & E:
C4 = OPTC4: Lonworks
On Board Base RS485 Communications:
BACnet MS/TP = MS/TP = Master Slave / Token Protocol (Universal BACnet)
RS 485 ModbusRTU RS485, ASCII or RTU, remote terminal unit 32 Nodes
On Board Ethernet Based Communications:
BACnet/IP Ethernet Industrial Protocol
M = Modbus/TCP Transmission Control Protocol (Ethernet Based) Note
All Boards are Varnished

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hmx01134nap3Hmx01131nais

Table of Contents