Ac Output Wiring; Figure 2-9, Ac Wiring Connections (Mms1012 Model) - Magnum Energy MMS Series Owner's Manual

Table of Contents

Advertisement

Installation
AC
Ground
In/Out
(green)
AC
INPUT

Figure 2-9, AC Wiring Connections (MMS1012 model)

2.4.6 AC Output Wiring

CAUTION: The inverter's AC output must never be
connected to an AC power source. This will cause severe
damage to the inverter and is not covered under warranty.
Info: When using the MMS Series inverter in an RV
application—under certain conditions and provided that
the wire is properly sized for the protecting breaker—
RVIA wiring standards will permit the breaker in the main
distribution panel and/or the supplemental breakers on the
inverter to provide adequate protection for the AC output
wiring. For more information on these requirements, refer
to the RVIA (www.rvia.org).
To hardwire the AC output of the MMS Series inverter:
1. Remove the 1/2" knockout on the AC Output Connection
(Figure 1-3, Item 9)—use a utility knife to cut thru the round slot.
2. Discard this knockout and install a 1/2" strain relief in the AC
Output opening. You may need to fi le the opening edge for
proper fi t.
3. Run a 2-conductor plus ground cable through the strain relief in
the AC OUT opening. Refer to Table 2-2 for the minimum wire size
and the overcurrent protection required for the AC output wiring.
4. Remove about two inches (5.1 cm) of the insulating jacket from
the AC cable, and then separate the three wires and strip about
3/4" (1.9 cm) of insulation from each wire.
24
Neutral to
Ground
Connection
Strain
reliefs
Neutral
Hot
In
In
(white)
(black)
Hot
Out
(red)
Neutral Out
(white w/
black
stripe)
AC
OUTPUT