Table 3-2, Inverter/Charger Default Settings - Magnum Energy MMS Series Owner's Manual

Table of Contents

Advertisement

Operation
04 Battery Type: This setting identifi es the type of batteries being
used in the system. This provides information to the charger to
determine what voltage level to use to charge the batteries.
05 Charge Rate:
limit the amount of current that the charger can use (leaving more
current available to power loads); or, to ensure small battery banks
are not overheated because of a charge rate that is too high.
06 VAC Dropout: Sets the minimum AC voltage that must be present
on the AC input before the unit transfers from Standby mode to
Inverter mode. This protects the AC loads from utility outages and
brown-outs.
The ME-RC50 remote also provides the following features:
allows you to enable an equalize charge for certain battery types
displays the inverter/charger's operating status
displays fault information for troubleshooting

Table 3-2, Inverter/Charger Default Settings

Function
Search Watts
LowBatCutOut
Battery AmpHrs
Battery Type
Charge Rate
VAC Dropout
38
This setting can be used to turn off the charger, or
(Absorb Time = 90 minutes)
Flooded - Liquid Lead Acid
(Absorb = 14.6 VDC, Float = 13.4 VDC)
Default Settings
5W
10.0 VDC
400 AmpHrs
100%
80VAC
© 2017 Sensata Technologies