Table 2-1, Wire/Overcurrent Device - Magnum Energy MMS Series Owner's Manual

Table of Contents

Advertisement

Installation

Table 2-1, Wire/Overcurrent Device

Maximum Continuous
Current
DC Grounding Electrode
Wire Size
Minimum DC Wire Size
(75˚C rating in free air)
Maximum DC Fuse Size
5 ft (1.5 m)
or less =
Increased
5 to 10 ft
size for
longer
(1.5 to 3.0 m) =
distance
10 to 15 ft
(3.0 to 4.6m) =
Note
– Based on the inverter's continuous power rating at the lowest
1
input voltage with an inverter ineffi ciency factored in.
Note
– Per the NEC, the DC grounding electrode conductor can be a #6
2
AWG (13.3 mm²) conductor if that is the only connection to the grounding
electrode and that grounding electrode is a pipe, rod, or plate electrode.
Note
– Copper wire rated with 75°C (167°F) insulation at an ambient
3
temperature of 30°C (86°F), with a multiple cable fi ll factor (0.8) de-
rating (if needed).
Note
– The next larger standard size overcurrent device may be used
4
if the de-rated cable ampacity falls between the standard overcurrent
devices found in the NEC.
16
MMS1012
133 amps
1
#6 AWG
(13.3 mm²)
2
#2 AWG
3
(33.6 mm²)
[170 amps]
150 amps with
4
time delay
#2 AWG
(33.6 mm²)
#2 AWG
(33.6 mm²)
#1 AWG
(42.4 mm²)
Inverter Model
MMS1012-G
133 amps
#6 AWG
(13.3 mm²)
#2 AWG
(33.6 mm²
[170 amps]
150 amps with
time delay
#2 AWG
(33.6 mm²)
#2 AWG
(33.6 mm²)
#1 AWG
(42.4 mm²)
© 2017 Sensata Technologies