Festo CPV -GE-DN2-8 Electronic Manual page 116

Cpv valve terminal with direct connection
Hide thumbs Also See for CPV -GE-DN2-8:
Table of Contents

Advertisement

B. DeviceNet objects
B.1.9 Structure of the diagnostic byte
Module
Bit 7
V
Load
CPV Direct
basic unit
CP valve
terminal in the
extension
Input module
Output module
– O module: CP connection interrupted at output module
– I module:
CP connection interrupted at input module
– Sc/o:
Short circuit/overload at output module (see chapter 3.5.1)
– V
:
Load voltage failure at output module
off
– V
:
Operating voltage failure at input module or sensors, short circuit/overload of sensor
sen
supply (see chapter 3.5.2)
Load voltage of valve coils < 20.4 V
– V
:
tol
– CM:
Condition Monitoring. At least one valve counter has exceeded the limit
Power supply of the CPV Direct < 20.4 V
– V
:
Load
B-12
The diagnostic byte gives information on recognizable errors
of the CPV Direct and of the modules in the extension.
Bit 6
Bit 5
Bit 4
CM
V
V
tol
sen
Further information can be found in chapter 3.4.
Bit 3
Bit 2
Bit 1
V
I mod.
Short
off
circuit/
overload
Festo P.BE-CP-DN2-EN en 0107NH
Bit 0
O mod.