that the first two bits have the state '0'. When both bits have the state '1', the
value 1 is added to the decimal measured value indicated in the table.
Some fieldbus systems can process input channel status information by means
of a status byte.
This status byte can be displayed via the starting tool WAGO-I/O-CHECK 2.
However, processing via the coupler / controller is optional, which means that
accessing or parsing the status information depends on the fieldbus system.
Attention
The representation of the process data of some I/O modules or their variations
in the process image depends on the fieldbus coupler/-controller used. Please
take this information as well as the particular design of the respective
control/status bytes from the section "Fieldbus Specific Design of the Process
Data" included in the description concerning the process image of the
corresponding coupler/controller.
2.1.1.6.1

Standard Format

For the standard module 750-483, the input voltage ranging from 0 V to
30 V is scaled on the numerical values ranging from 0x0000 to 0x7FFF.
WAGO-I/O-SYSTEM 750
I/O Modules
750-483 [2 AI DC 0-30 V, Differential Measurement Input]
Process values of module 750-483
Input voltage
0 V - 30 V
<-1
'0000.0000.0000.0000'
<0
'0000.0000.0000.0000'
0
'0000.0000.0000.000X'
5
'0001.0101.0101.010X'
10
'0010.1010.1010.101X'
15
'0100.0000.0000.000X'
20
'0101.0101.0101.010X'
25
'0110.1010.1010.101X'
30
'0111.1111.1111.1111'
>30
'0111.1111.1111.1111'
>31
'0111.1111.1111.1111'
numerical value
binary
hex.
0x0000
0x0000
0x0000
0x1554
0x2AAA
0x4000
0x5554
0x6AAA
0x7FFF
0x7FFF
0x7FFF
• 15
Process Image
Status-
LED
byte
Error
dec.
hex.
AI 1, 2
0
0x41
on
0
0x00
off
0
0x00
off
5460
0x00
off
10920
0x00
off
16384
0x00
off
21844
0x00
off
27304
0x00
off
32767
0x00
off
32767
0x00
off
32767
0x42
on