Changing the Direction / Fan Speed
Screen 1 Monitoring
Screen 2 Operation
Screen 3 Advanced Settings
21
2
4
8
7
Change the air direction or volume of air
1
conditioners.
On the Monitoring screen, operation is allowed
with either Icon or List as the display type.
The air direction or volume can be changed by
zone or by group.
[Procedure]
1.
On Screen 1 Monitoring, select a zone
or a group from the button q.
3
2.
Select a zone or a group of which the
air direction or volume is to be reset w.
3.
Press the [Configure] button e.
Screen 2 Operation is displayed.
4.
Press the [Advanced Settings] button r.
Screen 3 Advance Settings is displayed.
5.
Set the direction with the pull-down
menu y.
The larger the value for airflow direction
setting (0 - 6), the closer to vertical the
direction becomes. The value 7 indicates
automatic swing.
(Note: See the figure below.)
The description given above may not
exactly apply depending on the model.
Check the airflow direction sign on the
remote control after operation.
Select the Fan Speed with the pull-down
menu t.
Then press the [OK] button u.
To cancel the setting, press the
[Cancel] button.
Screen 2 Operation is displayed again.
6.
Then press the [OK] button i on Screen
2 Operation.
To cancel the setting, press the
[Cancel] button.
Note: Guidelines for airflow direction value and
actual direction
Indoor unit
5
0
6
4
5
6
7: Airflow direction auto