Specifications; Appendix - Delta 100kW PCS Installation Manual

Power conditioning system
Table of Contents

Advertisement

Appendix

Specifications

Table 14: Technical Specifications of Delta 100kW PCS
Item
Grid-tied Operation
Rated Grid Voltage
Grid Voltage Range
Rated Grid Frequency
Frequency Range
Rated AC Power
Rated AC Current
Max. Continuous AC Current
Current THD
Power Factor
Charging-discharging Transfer Time < 100 ms (±90% rated power)
Power Response Time
Battery Input Performance
DC Voltage Range
Rated DC Voltage
Rated Discharge Power
Rated Charge Power
Max. Discharge DC Current
Max. Charge DC Current
Standalone Mode Performance
Rated Output Voltage
Rated Output Power
Rated Output Current
Rated Output Frequency
Power Factor
Output Voltage Accuracy
Voltage Symmetry
Output Voltage THD
Installation Manual
400 Vac, 3 phase 3 wire
320 to 440 Vac (VDE-AR-N4105)
312 to 450 Vac (AS/NZS 4777.2)
50 Hz
47.5 to 51.5 Hz (VDE-AR-N4105)
47 to 52 Hz (AS/NZS 4777.2, Australia)
45 to 52 Hz (AS/NZS 4777.2, New Zealand)
100 kVA
144.3 A
160.4 Arms
< 3% at rated power (VDE-AR-N4105 and AS/NZS 4777.2
Compliant)
-1 to 1, continuously adjustable
< 40 ms (0~100% rated power)
750 to 1,000 Vdc
900 Vdc
103 kW
97 kW
137.3 A (103 kW @ 750 Vdc)
129.3A (97 kW @ 750 Vdc)
400 Vac, 3P3W (In 3P4W case, extra Dyn transformer
needed)
100 kVA/100 kW
144.3 A
50 Hz ± 1%
0.8 to 1
1%
± 1%, @ 100% linear balanced load
< 3% @ 12.5 ~ 100% liner load
< 5% @ 12.5 ~ 100% non-liner load (Crest factor ≤ 2.0)
61
Description
Appendix