Auxiliary Power Interface Connector (CNJ5)
CNJ5 is located on J board called Interface board, shown in the following figure. It is used for
alternative auxiliary power input with 24Vdc 0.5A. Connect two 1.32 ~ 0.326 mm
connector as the pin assignment table below. Customer can run PCS in black start mode via this
terminal.
Table 11: For Black Start Use (Optional) (Use 2-pin)
Item
1: Vdc +
CNJ5
2: Vdc -

Black Start

1. After the auxiliary power is connected, the communication part of PCS starts to work.
2. Make sure you connect the communication cable between the BMS and the PCS correctly and
the PCS battery manufacturer type is set correctly. The default setting is LGC battery in the
Modbus setting.
3. Turn on the auxiliary power of the BMS.
4. The BMS establishes a communication connection with the PCS, and the batter outputs the HV
DC.
5. The DC input of the PCS comes from the battery. Enters the island operation mode, starts the
PCS, establishes the microgrid, and completes the black start.
Demand Response Management (RJ45)

Demand Response Management

The inverter provides a RJ45 port to support the connection to a demand response enabling device
(DRED). The support is required as the DRED asserts demand response modes (DRMs). When the
inverter detects a demand response command, it initiates a response. The following table lists the
DRMs supported by the inverter.
Note:
The mandatory respond mode is DRM0 (standby), while support for the remaining listed
modes is option and may not be applicable for all models.
Table 12: Demand Response Modes (DRMs)
Mode
DRM0
The inverter is in standby.
DRM1
Power consumption from the grid is 0.
DRM2
Power consumption from the grid is no more than 50% of the rated power.
Power consumption from the grid is no more than 75% of the rated power, while source
DRM3
reactive power enabled.
DRM4
Increased power consumption, but subject to the constraints from other active DRMs.
DRM5
Do not generate power
DRM6
The export power to the grid is no more than 50% of the rated power.
Installation Manual
Pin Assignment
49
Notes
24Vdc, 0.5A;
For Black Start
Description
Wiring Instructions
2
wires to the 2-pins