Delta 100kW PCS Installation Manual page 66

Power conditioning system
Table of Contents

Advertisement

Table 14: Technical Specifications of Delta 100kW PCS (Continued)
Item
Output Voltage Regulation
Crest Factor
Max Altitude
Environment
Operating Temperature
Storage Temperature
Humidity
Cooling
Pollution Degree
Acoustic Noise
IP Degree
Interface & Communication
Digital I/O
User Interface
Emergency Stop
Communication
System Characteristic
Peak Efficiency
Sleep Mode Loss
Operation Mode
Dimensions (W x D x H)
(excl. Package)
Net Weight (excl. Package)
Standard Compliance
Certificate
Applicable Battery Chemistry
Installation Manual
< 10%, at dynamic; Recovering within tolerance in 100 ms
2.0 @ rated power
3,000 m (9,843 ft)
Thermal derating above 2,000 m (6,561.68 ft.)
≤ 2,000 m: -25 ~ 60ºC (-13 ~ 140ºF), derating > 50ºC (3%/ºC)
> 2,000 m: -25 ~ 40ºC (-13 ~ 104ºF),
-25 ~ 70ºC (-13 ~ 158ºF)
0 to 95% RH, no-condensing
Fan cooled, speed controlled and alarmed signal
3
< 72 dBA @ 1 m (3.3 ft)
IP55
3 x Input, 0 - 24 V
2 x Output relays
4.9 inch LCD screen with push button, Fault LEDs
Local EPO button & remote control
RS-485 / Modbus RTU, CAN
97.2%
< 25 W
Demand charge management (Power Dispatch)
Load shifting for Time-of-Use saving
Power quality improvement (P-Q Control, Frequency
Regulation)
Emergency backup power
600 mm x 800 mm x 1,766 mm / 23.6 in x 31.5 in x 69.5 in
310 kg / 683 lbs
IEC 62477-1, VDE-AR-N 4105, AS 62040.1.1,
AS/NZS 4777.2, IEC 61000-6-2/-4
Lithium-ion, lead-acid, flow battery
62
Description
Appendix

Hide quick links: