Bms Communication Connector - Delta 100kW PCS Installation Manual

Power conditioning system
Table of Contents

Advertisement

BMS Communication Connector (CNJ13)
The CNJ13 connector is for communication between PCS and BMS. Communication with BMS is
handled in two ways, RS485/Modbus or CANbus. RS485 requires three prepared 1.32 mm
connected to pins 1 to 3 on the 6-pin connector from the accessory kit. For CANbus, connect two
2
prepared 1.32 mm
wires to pins 5 and 6.
Table 7: CNJ13 Pin Assignment
Item
1: RS485-B3
2: RS485-A3
3: GND5
CNJ13
4: NC
5: CAN-H4
6: CAN-L4
Note:
CAN and Modbus/RTU (RS485) are both provided for different vendors of battery. When
Modbus/TCP IP (Ethernet) in system configuration is required to communicate with PCS,
install an Ethernet converter accordingly connected to CNJ13 in PCS.
Installation Manual
Pin 1
Figure 46. CNJ13 Pin Assignment
Pin Assignment
46
Notes
For BMS
For BMS (optional)
Wiring Instructions
2
wires

Hide quick links: