Communication Connector (CNJ11, CNJ12)
The CNJ11 and CNJ12 connectors are for communication with ESS controller or with other PCS in
parallel operation. Prepare two RJ45 connectors and six 1.32 mm
wires to the pin 1~2 and pin 4~7 of the RJ45 connector as the graphic and pin assignment below:
Table 9: CNJ11, CNJ12 Pin Assignment
Item
1: RS485-A2
2: RS485-B2
3: NC
CNJ11, CNJ12
5: CAN-H2
6: CAN-L2
7: CAN-H3
8: CAN-L3
Table 10: Used for Upper Controller (Use 3-pin)
Item
1: RS485A2
2: RS485B2
CNJ7
3: NA
Note:
CNJ11 and CNJ12 are used for parallel operation more than one PCS. When multiple PCSs
are parallel operated, the network cable should be connected hand by hand, with CNJ11 or
CNJ12 of the first PCS is connected to upper controller and the terminal resistors should be
inserted to CNJ11 or CNJ12 of the last one.
Installation Manual
CNJ12
P1
PIN 1
PIN 8
Figure 48. CNJ11, CNJ12 Pin Assignment
Pin Assignment
Pin Assignment
48
2
wires for each, and connect the
CNJ11
P2
PIN 1
PIN 8
Notes
For ESS Controller
For PCS parallel
For voltage detection
Notes
The same RS485 terminal as pin1 and pin2 of
CNJ11/CNJ12, for ESS Controller/Site Controller/
Local Controller/PC.
Used for installation when only one PCS.
Wiring Instructions