Data sets
A.15 Read DS204 device parameter 2
A.15

Read DS204 device parameter 2

DS204 contains the second part of the incorrect parameters with which the motor starter is
working.
The defaults appear in italics in the Value range column.
Object
Byte.Bit
number
18 0.0 - 0.3
- 0.4 - 0.7
2210 1
- 2 - 3
- 4 - 5
17 6
- 7
2213 8
2214 9
200
Range of values
1
... 7.5 s/0.5 s
[2 ... 15]
Default value is [2]: 1 s.
[0]: Reserved
0 ... 99 %/1 %
[0 ... 99]
Deactivated
[0]:
[0]: Reserved
[0]: Reserved
150 ... 1500 %/50 %
[3 ... 20]
Default value is [16]:
800 %
As of firmware version
V1.2.0
[0]: Reserved
18.75 ... 100 %/3.125 %
[6 ... 32]
[0]: Deactivated
Default value is [7]:
21.875 %
50 ... 400 %/3.125 %
[16 ... 128]
[0]: Deactivated
Default value is [36]:
112.5 %
Meaning
Blocking time
Reserved
Warning limit - motor heating Overload protection (Page 76)
Reserved
Reserved
Blocking current
Reserved
Lower current warning limit
Upper current warning limit
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
See Chapter ...
Blocking time and blocking current
(Page 95)
-
-
-
Blocking time and blocking current
(Page 95)
-
Upper/lower current warning limit
(Page 93)
Upper/lower current warning limit
(Page 93)
Motor starter (3RK1308‑0**00‑0CP0)