Error type
Fault text
channel
diagnostics
1083
(4227
)
Switching element
h
dec
overload
1084
(4228
)
Electronics supply
h
dec
voltage too low
1088
(4232
)
No switching element
h
dec
supply voltage
1095
(4245
)
Parameter error
h
dec
1096
(4246
)
Process image error
h
dec
10A5
(4261
)
Residual current
h
dec
100A
(4106
)
Test mode current flow Current is flowing in the motor feeder although the motor feeder is in test
h
dec
109D
(4253
)
Input Action
h
dec
109E
(4254
)
Emergency end
h
dec
position CW
001F
(31
)
Channel temporarily
h
dec
unavailable
109F
(4255
)
Emergency trip end
h
dec
position CCW
134B
(4939
)
Trip Reset not possible Trip reset is currently not possible (e.g. because the cooling phase is in
h
dec
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
Remedial measures
Switching element (switching contact, power semiconductor) too hot.
Check the ambient conditions linked to cooling. You might have to take
derating into consideration. Check the number of switching operations. Also
check whether the fan is working properly.
The supply voltage is below the permissible value.
Remedy: Check the power supply (load measurement, voltage range)
No supply voltage has been detected or the mechanical rotary interlock is not
in the READY position.
Remedy: Check the power supply to the switching elements and the cabling
or turn the mechanical rotary interlock to the READY position.
The module is not yet parameterized or is incorrectly parameterized or the
safety-related parameters have been rejected.
Remedy: Correct the parameterization.
The process image output (PIQ) contains invalid control bit combinations
(e.g. control bits for clockwise and counter-clockwise set simultaneously).
Remedy: Check and correct the process image output (PIQ).
No current flow is detected in the motor feeder after an ON command.
Possible causes: Phase failure, fault in the motor winding, fuse in the device
defective
Remedy: Check the motor feeder (main circuit) and the motor. Clear the
short-circuit in the system and replace the device.
mode or the test position. Possible causes: The main circuit is not interrupted
in test operation.
The cold start function of the ET 200SP motor starter is activated.
Remedy: Check the wiring or deactivate the cold start function
A warning or trip signal is active on at least one input.
Remedy: Check the application.
The "CW" emergency end position has been passed.
Remedy: Check the end position of the drive.
Wait until the firmware update is completed.
The "CCW" emergency end position has been passed.
Remedy: Check the end position of the drive.
progress).
Remedy: Repeat the action later (e.g. after the cooling time has elapsed).
Alarms/diagnostic messages
8.3 Interrupts
169