Functions
6.11 Inputs
Note
Change from NC contact to NO contact
If "Input n level" is changed from a normally closed contact to a normally open contact and
the associated "Input n action" is parameterized as "Trip without restart", the "Input tripping"
message bit is set and shut down accordingly in the case of an open input due to the input
delay!
Note
Applied input voltage
If input voltage is applied (input active), the value "1" is transferred to the controller
regardless of the "Input n level" parameter.
Input n action
Different actions can be triggered when an input signal is present. You can parameterize the
following actions dependent on "Input n level", "Input n signal" and "Mode".
Note
If "Input n-signal" = retentive, and "Input n-action" = motor CW/CCW, at least one input must
always be parameterized with input action "Tripping ..." or "Quick Stop". If this rule is
violated, the motor starter will reject the parameters with the relevant diagnostic message.
106
Motor starter (3RK1308‑0**00‑0CP0)