Response to removal of the 3DI/LC module:
Bit 2.5 is reset in the process image input if you remove the 3DI/LC module during operation.
You can evaluate the bit and thus indicate unintentional removal. The inputs are not
open-circuit-proof.
The motor can continue to run with the corresponding parameterization
When you remove the 3DI/LC module, the motor can continue to run with the appropriate
parameterization.
Input signal delay
The input signal delay is fixed at 10 ms.
Input n signal
You can use this device parameter to determine whether or not the input level of the inputs is
to be saved.
● Retentive, i.e. latching mode (edge evaluation)
Regardless of the input signal present, the action can only be deactivated again by a
further event and remains active even after cancellation until it is overwritten by another
action (e.g. process image of the outputs).
● Non-retentive, that is, jog (level evaluation)
This input action is active as long as the input is active.
Input n level
You use this device parameter to specify the input logic:
● NC contact
● NO contact
Note
Parameterization only as NO contact.
For "Input n action": "Emergency start", "Motor CW", "Motor CCW", "Cold start" and "Trip
reset", "Input n level" can only be parameterized as a NO contact.
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
WARNING
Functions
6.11 Inputs
105