Data sets
A.13 Read/write DS202 device parameter 2
A.13

Read/write DS202 device parameter 2

DS202 contains the second part of the device parameters.
If incorrect parameters are sent to the motor starter in DS202, these incorrect parameters
will also be reported back when reading DS202. In the case of incorrect parameters, the
object number of the first incorrect parameter is output in WORD 10 of DS92.
The defaults appear in italics in the Value range column.
Object
Byte.Bit
Range of values
number
1
18 0.0 - 0.3
[2 ... 15]
Default value is [2]: 1 s.
- 0.4 - 0.7 [0]: Reserved
2210 1
0 ... 99 %/1 %
[0 ... 99]
[0]:
- 2 - 3
[0]: Reserved
- 4 - 5
[0]: Reserved
17 6
150 ... 1500 %/50 %
[3 ... 20]
Default value is [16]: 800 %
As of firmware version
V1.2.0
- 7
[0]: Reserved
2213 8
18.75 ... 100 %/3.125 %
[6 ... 32]
[0]: Deactivated
Default value is [7]:
21.875 %
2214 9
50 ... 400 %/3.125 %
[16 ... 128]
[0]: Deactivated
Default value is [36]:
112.5 %
196
... 7.5 s/0.5 s
Deactivated
Meaning
Blocking time
Reserved
Warning limit - motor heating
Reserved
Reserved
Blocking current
Reserved
Lower current warning limit
Upper current warning limit
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
See Chapter ...
Blocking time and blocking
current (Page 95)
-
Overload protection (Page 76)
-
-
Blocking time and blocking
current (Page 95)
-
Upper/lower current warning
limit (Page 93)
Upper/lower current warning
limit (Page 93)
Motor starter (3RK1308‑0**00‑0CP0)