Siemens 3RK1308‑0 00‑0CP0 Series Equipment Manual page 147

Industrial controls et 200sp motor starter
Table of Contents

Advertisement

Input n signal
You use this device parameter to determine whether or not the input level of the digital inputs
is to be saved.
For more information, see Chapter Inputs (Page 104).
Load type
Here, you can specify whether the motor starter must protect a 1-phase load
(direct-on-line starters only) or a 3-phase load.
For more information, see Chapter Load type (Page 69).
Upper/lower current limit
You can enter a lower and/or an upper current limit value.
Note
The current limits are not activated for startup override until the CLASS time expires, e.g.
after 10 seconds for CLASS 10.
For more information, see Chapter Upper/lower current limit (Page 94).
Upper/lower current warning limit
You can enter a lower and/or an upper current warning limit value.
Note
The current limits are not activated for startup override until the CLASS time expires, e.g.
after 10 seconds for CLASS 10.
For more information, see Chapter Upper/lower current warning limit (Page 93).
Group error diagnostics
You use this parameter to determine whether diagnostics via PROFINET or PROFIBUS DP
(fault type) are enabled or disabled.
For more information, see Chapter Group fault diagnostics/group warning diagnostics
(Page 103).
General warning diagnostics
You use this device parameter to determine whether or not a maintenance alarm is
forwarded to the higher-level CPU.
For more information, see Chapter Group fault diagnostics/group warning diagnostics
(Page 103).
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
Parameters/address space
7.6 Declaration of parameters
147

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents