Commissioning mode

Commissioning mode is available for fail-safe ET 200SP motor starters.
When setting up a system, you can test the wiring without the functioning PROFINET or
PROFIBUS connection. Perform the test in commissioning mode.
The motor starter switches to commissioning mode in the following cases:
● After the power supply has been activated, the motor starter does not receive any
parameterization via the backplane bus.
● The DI module's "Local Control" switch is activated.
As soon as Local Control is active, the parameterization saved last is used when the
power supply is activated. Control via the DI module is possible after confirmation via the
TEST/RESET button.
To switch to commissioning mode in the case of fail-safe motor starters, confirm the change
with the blue button. During ATEX operation, additionally confirm the current parameters, as
described in chapter "Configuring ATEX operation (Page 151)".
If the motor starter receives valid parameterization via the backplane bus in commissioning
mode, the parameterization is placed in intermediate storage. The parameterization
becomes active when "Local Control" is terminated (motor OFF). The commissioning mode
is exited.
Inputs for commissioning
To ensure operation of a motor in the unparameterized state of the ET 200SP motor starter
with the aid of the 3DI/LC module, the input parameters in data record 201 are permanently
assigned the following values by default:
● DI1: Motor CW
● DI2: Motor CCW
● DI3: Cold start (fail-safe motor starters as of V1.2.0)
This pre-parameterization is overwritten when the ET 200SP motor starter is parameterized.