Parameters/address space

7.3 Parameterization using a GSD file

7.3
Parameterization using a GSD file
For the ET 200SP-IM155 interface module of the ET 200SP system, there are two different
GSD files, one for operation with PROFINET and one for operation with PROFIBUS. The
GSD and GSDML files can be used with STEP 7 V5.5 SP4 and higher, and TIA Portal
V13 SP1 and higher.
If you configure the ET 200SP motor starter in the PROFIBUS environment with GSD, and
the standard values in data set 202 have to be changed, then you create data set 202 via the
user program on initial commissioning of the starter. Transfer the data set to the PLC.
Parameterization with the PROFINET GSDML file
The ET 200SP motor starter can be fully configured with all parameters with the GSDML file
for PROFINET.
Parameterization with the PROFIBUS GSD file
Two parameter data sets (DS201 and DS202) are used for configuring the
ET 200SP motor starter. Only data set DS 201 is ever transferred as the startup data set
when using a PROFIBUS GSD.