Siemens 3RK1308‑0 00‑0CP0 Series Equipment Manual page 164

Industrial controls et 200sp motor starter
Table of Contents

Advertisement

Alarms/diagnostic messages
8.1 Status and error displays
LEDs
RN
ER
(RUN)
(ERROR)
Not
relevant
Flashes
at ≥ 2 Hz
OFF
On
OFF
Flashes
ST/OL (STATE/OVERLOAD) LED
Table 8- 2
Status display ST/OL
ST/OL LED
Motor operating state
Operation
On
STOP
Off
Overload
Flashes
at 0.5 Hz
164
MT
(MAINT)
Not
Error
relevant
PROFIenergy active
Flashes
Action required
Flashes
ON command for motor active
The motor is switched off.
It is not known whether the motor is still rotating or not.
The thermal motor model or device protection model has tripped.
Meaning
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
Explanation
Group fault
At least one Error alarm has been
transferred to the controller.
Possible causes:
Electronics supply voltage too low or
too high
Motor protection disconnection
Thermal overload of the
ET 200SP motor starter
Missing load voltage, phase
failure/missing load
The mechanical rotary interlock is
not in the READY position.
-
Ex motor (ATEX): New safety-related
parameters are available for release.
Meaning
Motor starter (3RK1308‑0**00‑0CP0)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents