Checking incoming parameters in "Manual local" mode
The incoming parameters are checked as follows in "Manual local" mode:
● When the motor is switched off:
The motor starter saves the parameter and accepts it only when the motor starter has
switched over to "Automatic" mode again. Only after changing to "Automatic" are the
parameters checked.
● When the motor is running:
– The parameters are not accepted by the motor starter, even if the motor starter
– The diagnosis "Parameters cannot be changed in ON state" is set in the
– The diagnosis "Group warning" is set.
– The motor is not switched off.
– A logbook entry is created
– The currently valid parameter values are retained.
Checking incoming parameters in "Manual bus" mode
The incoming parameters are not accepted and saved in "Manual bus" mode.
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
changes later to "Automatic" mode.
DS75 logbook - Read events (Page 184).
Parameters/address space
7.5 Data plausibility check