Operating Modes - Siemens 3RK1308‑0 00‑0CP0 Series Equipment Manual

Industrial controls et 200sp motor starter
Table of Contents

Advertisement

Functions
6.4 Motor control
t
3
t
4
t
W
Figure 6-3
6.4.4

Operating modes

The following modes are available (in ascending order of priority):
● Operating mode: Automatic (lowest priority)
The motor starter can only be controlled with the PLC via the fieldbus.
Automatic mode is activated automatically when communication with the interface
module or the higher-level CPU is established.
● Operating mode: Manual bus: Controlling the motor starter by means of software,
e.g. TIA Portal V16, via fieldbus is possible
● Operating mode: Manual local via the 3DI/LC module (highest priority)
The motor starter can be controlled as follows:
– Set the "Local Control" (LC on the 3DI/LC module) input to activate
– Also set a digital input on the 3DI/LC module (1, 2 or 3, depending on the
Using the LED "MAN", the message bits in the Address space (Page 158) and the
DS92 Read device diagnostics (Page 186), you detect which control source currently has
control priority:
● Operating mode: Automatic ("MAN" LED off)
● Operating mode: Manual local ("MAN" LED on)
74
Interlock time: 150 ms + 5 ms time slice run
ON-delay
Fail-safe motor starters: 25 ms
HF motor starter: 20 ms
Recovery time t
+ t
+ t
0
2
3
Fail-safe motor starters: t
HF motor starter: t0 + 190 ms
Control command reaction times
manual local mode.
parameterization) to "Motor CW" or "Motor CCW", for example.
+ 210 ms
0
1)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
Motor starter (3RK1308‑0**00‑0CP0)