Set-Back Operation - Samson TROVIS 5573 Mounting And Operating Instructions

Heating and district heating controller
Table of Contents

Advertisement

Functions of the DHW circuit
set point has reached 5 °C at the minimum. How strongly the controller responds is deter-
mined by the 'Influence factor KP'.
When 'Activate priority in the event of a system deviation' is set to 0, the priority operation is
started regardless of the time and temperature in the system. The control valve of the corre-
sponding heating circuit is closed.
Functions
Priority through reverse control
Priority through set-back
operation
7.8.2

Set-back operation

In all systems with DHW heating and at least one heating circuit with a control valve, DHW
heating can be given priority by applying set-back operation. With the setting CO4 > F09 -
1, the temperature is monitored at sensor VFx in the DHW circuit.
In systems without sensor VFx in the DHW circuit (e.g. Anl 4.5, 11.0), the temperature is
monitored directly at storage tank sensor SF1. If system deviations still occur after the time set
in 'Activate priority in the event of a system deviation' has elapsed, the selected heating cir-
cuit with the control valve is set to reduced operation.
When 'Activate priority in the event of a system deviation' is set to 0, the priority operation is
started regardless of the time and temperature in the system. of all heating circuits.
Functions
Priority through reverse control
Priority through set-back
operation
84
WE
Configuration
0
CO4 > F08 - 1
2 min
Activate priority in the event of a system deviation: 0 to
1.0
10 min
HC2
KP (influence factor): 0.1 to 10.0
Control circuit selection: HC1, HC2, HC1+HC2
0
CO4 > F09 - 0
WE
Configuration
0
CO4 > F08 - 0
0
CO4 > F09 - 1
2 min
Activate priority in the event of a system deviation: 0 to
HC2
10 min
Control circuit selection: HC1, HC2, HC1+HC2
EB 5573 EN