Start-up

3.2 Activating and deactivating functions

A function is activated or deactivated in the associated function block. 0 to 24 at the top of
the display represent the function block numbers. When a configuration level is opened, the
activated function blocks are indicated by a black square on the right-hand side below the
function block number. For more details on function blocks, see section 13.1.
The functions are grouped by topics:
− CO1:
HC1 (heating circuit 1)
− CO2:
HC2 (heating circuit 2)
− CO4:
DHW circuit
− CO5:
System-wide
− CO6:
Modbus communication
1. Turn the rotary switch to
Reading: 0 0 0 0
2. Enter valid key number [q].
3. Confirm key number [Û].
Reading: PA_
4. Select configuration level [q].
5. Open configuration level [Û].
6. Select function block [q].
Activated function blocks are marked '- 1'.
Deactivated function blocks are marked '- 0'.
7. Activate editing mode for the function block [Û].
blinks.
8. Activate function block [q].
Reading: F__ - 1
An activated function block is indicated by a black square below (right) the function
block number at the top of the controller display.
or:
Deactivate function block [q].
Reading: F__ - 0
24
(parameter and configuration level).
EB 5573 EN