2.8.2

Entering vacations

The system runs constantly in reduced mode during vacation periods. A maximum of ten va-
cation periods can be entered. Each vacation period can be separately assigned to the heat-
ing circuits HC1, HC2 and/or the DHW circuit.
Parameters
Vacation period (START, STOP)
Proceed as follows:
EB 5573 EN
WE
Level: value range
Extended information level: 01.01 to 31.12
1. In the extended information level (normal switch position
) select the data point for vacations [q].
Reading:
2. Open data point for public holidays [Û].
Reading: START
3. Select – –.– – on the display [q] (if applicable).
4. Activate editing mode for the start date of the vacation
[Û].
and
blink.
5. Set the start date of the vacation [q].
6. Confirm the start date setting [Û].
Reading: STOP, – –.– –
7. Set the end date of the vacation [q].
8. Confirm the end date setting [Û].
Black squares at the top of the display indicate the
assignment of the vacation periods to the individual
control circuits.
Operation
19