Functions of the heating circuit
In systems in which the drying function had to be interrupted due to DHW heating (e.g. sys-
tem Anl 2.1, see section 5), storage tank charging does not occur while the drying function is
active, provided it is not used for frost protection of the storage tank.
Note
The function block parameters can only be accessed after after starting the function by deac-
tivating and activating the function block again.
Functions
Underfloor heating/drying of jointless
floors

6.4 Deactivation depending on outdoor temperature

6.4.1

OT deactivation value in rated operation

The associated heating circuit is immediately switched off when the outdoor temperature ex-
ceeds the limit 'OT deactivation value in rated operation'. The valve is closed and the pump
is switched off after t = 2 x Valve transit time. The heating is immediately switched on again
when the outdoor temperature falls below the limit (minus 0.5 °C hysteresis).
The default setting causes the system to be switched off during warm weather at an outdoor
temperature of 22 °C.
Parameters
OT deactivation value in rated operation
6.4.2

OT deactivation value in reduced operation

The associated heating circuit is immediately switched off when the outdoor temperature ex-
ceeds the limit 'OT deactivation value in reduced operation'. The valve is closed and the
pump is switched off after t = 2 x Valve transit time. The heating is immediately switched on
again when the outdoor temperature falls below the limit (minus 0.5 °C hysteresis).
64
WE
Configuration
0
CO1, 2 > F05 - 1
25.0 °C
Start temperature: 20.0 to 60.0 °C
0
Hold (days): 0 to 10 days
5.0 °C
Temp. rise/day: 0.0 to 10.0 °C
45.0 °C
Maximum temperature: 25.0 to 60.0 °C
4
Hold (days): 0 to 10 days
0.0 °C
Temp. reduction/day: 0.0 to 10.0 °C
SToP
STArT,

WE
Parameter level: configuration
22.0 °C
PA1, 2: 0.0 to 50.0 °C
STArT,
STArT,


STArT