Functions Of The Heating Circuit; Outdoor-Temperature-Controlled Control - Samson TROVIS 5573 Mounting And Operating Instructions

Heating and district heating controller
Table of Contents

Advertisement

Functions of the heating circuit

6 Functions of the heating circuit
Which controller functions are available depends on the selected system code number (Anl).
See section 5.

6.1 Outdoor-temperature-controlled control

When outdoor-temperature-compensated control is used, the flow temperature is controlled
based on the outdoor temperature. The heating characteristic in the controller defines the
flow temperature set point as a function of the outdoor temperature (see Fig. 5). The outdoor
temperature required for outdoor-temperature-compensated control can either be measured
at an outdoor sensor or received over the 0 to 10 V input.
t
[ ° C]
VL
150
140
130
120
110
100
90
80
70
60
50
40
30
20
20
16
12
8
Fig. 5: Gradient characteristics
Functions
Outdoor sensor AF1
Outdoor temperature received as 0 to
10 V signal
58
3.2
4
0
–4
–8
–12
–16
WE
2.9
2.6
–20
–24 –28 –32 –36 –40
Configuration
1
CO1 > F02 - 1
0
CO5 > F23 - 1
AE
Direction: AE (receive)
–20 °C
Lower transmission range: –50 to +100 °C
+50 °C
Upper transmission range: –50 to +100 °C
2.4
2.2
2.0
1.8
1.6
1.4
t
: Flow temperature
1.2
VL
t
: Outdoor temperature
1.0
A
0.8
0.6
0.4
0.2
t
A
[ ° C]
EB 5573 EN