Remote Operation; Optimization - Samson TROVIS 5573 Mounting And Operating Instructions

Heating and district heating controller
Table of Contents

Advertisement

Functions of the heating circuit

6.7 Remote operation

Apart from measuring the room temperature, the Types 5257-5 and 5257-21 Room Panels
(Pt 1000 sensor) as well as Type 5244 Room Panel (PTC sensor) provide the following oppor-
tunities of influencing the control process:
− Selecting the operating mode: −
− Set point correction: during rated operation, the room temperature set point can be in-
creased or reduced by up to 5 °C using a continuously adjustable rotary knob.
With an activated room sensor, the measured room temperature is displayed when the re-
mote operation is connected and activated. Nevertheless, it is not used for control when ei-
ther the optimization, adaptation or flash adaptation function is activated.
Type 5257-5
Type 5257-51
Terminal 1
Terminal 2
Terminal 3
Fig. 7: Wiring plan for Types 5257-5 and 5257-51 Room Panels to TROVIS 5573 for HC1 and
HC2
Functions
Room sensor RF1/RF2

6.8 Optimization

This function requires the use of a room sensor. Depending on the building characteristics,
the controller determines and adapts the required advance heating time (maximum 8 hours)
to ensure that the desired 'Day set point' (rated room temperature) has been reached in the
reference room when the time-of-use starts. During the advance heating period, the controller
heats with the max. flow temperature. This temperature is built up in steps of 10 °C. As soon
as the 'Day set point' has been reached, outdoor-temperature-compensated control is activat-
ed.
68
Automatic mode
Day mode
Night mode
TROVIS 5573
HC1
HC2
Terminal 5
Terminal 3
Terminal 12
Terminal 12
Terminal 9
Terminal 10
WE
0
Configuration
CO1, 2 > F01 - 1
EB 5573 EN