Operation

5.3 Entering day and night set points

The day set points apply during day mode (rated operation) and during times-of-use pro-
grammed for automatic mode.
The night set points apply during night mode (reduced operation) and outside the times-of-
use programmed for automatic mode.
The desired room temperature for the day and night set points can be programmed.
Switch position
Parameters
HC1 room temperature
HC2 room temperature
HC3 room temperature
HC11 room temperature
HC12 room temperature
HC13 room temperature
DHW temperature
HC1 OT deactivation value
HC2 OT deactivation value
HC3 OT deactivation value
HC11 OT deactivation value
HC12 OT deactivation value
HC13 OT deactivation value
Switch position
Parameters
HC1 room temperature
HC2 room temperature
HC3 room temperature
HC11 room temperature
HC12 room temperature
HC13 room temperature
DHW temperature
20
WE
Value range
20.0 °C
0.0 to 40.0 °C
20.0 °C
0.0 to 40.0 °C
20.0 °C
0.0 to 40.0 °C
20.0 °C
0.0 to 40.0 °C
20.0 °C
0.0 to 40.0 °C
20.0 °C
0.0 to 40.0 °C
60.0 °C
Min. to max. DHW temperature
22.0 °C
0.0 to 50.0 °C
22.0 °C
0.0 to 50.0 °C
22.0 °C
0.0 to 50.0 °C
22.0 °C
0.0 to 50.0 °C
22.0 °C
0.0 to 50.0 °C
22.0 °C
0.0 to 50.0 °C
WE
Value range
15.0 °C
0.0 to 40.0 °C
15.0 °C
0.0 to 40.0 °C
15.0 °C
0.0 to 40.0 °C
15.0 °C
0.0 to 40.0 °C
15.0 °C
0.0 to 40.0 °C
15.0 °C
0.0 to 40.0 °C
40.0 °C
Min. to max. DHW temperature
KA 5578-E EN