Error during operation
9.3 Temperature monitoring
When a system deviation greater than 10 °C persists in a control circuit for 30 minutes, an
Err 6 message (temperature monitoring alarm) is generated.
Functions
Temperature monitoring
9.4 Error status register
The error status register is used to indicate controller or system errors.
Error message
Err 1
Err 2
Err 3
Err 4
Err 5
Err 6
Err 7
Err 8
Err 9
100
WE
0
Meaning
Sensor failure
–
Disinfection temperature not reached
Max. charging temperature reached
–
Temperature monitor alarm
Unauthorized access occurred
Error message of a binary input
–
Example: Value of error status register when a sensor fails and a
Configuration
CO5 > F19 - 1
temperature monitoring alarm =
Decimal value
1
2
4
8
16
32
64
128
256
Total
EB 5573 EN
1
32
33